BYD Battery-Box Premium HVM + Fronius Gen24 (Modbus TCP)

Reference setup: BYD Battery-Box Premium HVM (12.8 kWh) controlled through a Fronius Gen24 inverter via Modbus TCP, Nordpool prices, Fronius SolarNet consumption sensor, Open-Meteo Solar Forecast.

Architecture

The BYD battery is not controlled directly — all control goes through the Fronius Gen24 via Modbus TCP (sunspec storage model):

Home Assistant ── modbus.write_register (hub: gen24, slave: 1)
   └─ Fronius Gen24 ── internal BYD interface ── BYD Battery-Box Premium HVM

Modbus hub (configuration.yaml)

modbus:
  - name: gen24
    type: tcp
    host: <inverter-ip>
    port: 502

Home Assistant 2026.9 (Fronius Modbus in core)

From 2026.9 the built-in Fronius integration (Solar API) also talks Modbus TCP (SunSpec) when the inverter has it enabled. Existing config entries are migrated to port 502 automatically — no extra setup.

Keep the YAML hub and the scripts below. Do not drive the new core number/switch entities (AC power limit, Battery charge/discharge power limit, Battery minimum reserve, Battery grid charging) in parallel: they write the same SunSpec registers (40232/40236, 40348–40356, 40360) and will fight the SBP plan. Reading them is fine; they catch up on the next Fronius poll (~1 min).

The core entities are limits and permissions, not force-charge / force-export. The negative (two's-complement) OutWRte/InWRte rates that force a charge or an export are not exposed, so these scripts cannot be replaced 1:1.

The Gen24 accepts only a handful of simultaneous Modbus TCP sessions (YAML hub, core Fronius, often EVCC). After upgrading, check that modbus.write_register still succeeds. Core claims it shares the connection when host+port match; YAML hubs historically opened their own socket — treat a second session as possible until proven otherwise.

Battery charging energy total / Battery discharging energy total from core Fronius are DC counters on the device (no Riemann, survive restarts) and are a better pair for SBP's optional actual-savings inputs than integrating power.

Relevant Modbus registers (Fronius Gen24, slave 1)

Register Name Description
40345 WChaMax Maximum charge power in W (e.g. 12800), the base for both rates
40348 StorCtl_Mod Bitfield that arms the rate limits: bit 0 = InWRte (charge limit), bit 1 = OutWRte (discharge limit). 0 none, 1 charge limit, 2 discharge limit, 3 both
40350 MinRsvPct Minimum SOC reserve ×100 (500 = 5 %, 9900 = 99 %). The Gen24 tops a battery below it up from the grid, but only at ~500 W
40355 OutWRte Discharge limit, % of WChaMax ×100 (10000 = 100 %, signed). 0 blocks discharging; a negative value (65536 − rate) forces charging at that rate. Needs bit 1
40356 InWRte Charge limit, % of WChaMax ×100 (10000 = 100 %, signed). 0 blocks charging; a negative value forces discharging at that rate. Needs bit 0
40358 InOutWRte_RvrtTms Revert timeout in seconds for InWRte/OutWRte. 0 = the limits stay until the next write; any other value drops them back to normal operation after that many seconds
40360 ChaGriSet Grid charging: 1 = allowed (required for forced charging), 0 = PV only

The rates only take effect while their bit is set in StorCtl_Mod. Measured on the reference installation (night, 21 °C battery, 3000 W requested): StorCtl_Mod 1 with a negative OutWRte charged at only ~500 W (the MinRsvPct top-up), StorCtl_Mod 2 charged at 3000 W. EVCC's Gen24 template uses the same semantics (hold = StorCtl_Mod 2 + OutWRte 0; charge = StorCtl_Mod 2 + negative OutWRte) and rewrites StorCtl_Mod when a car starts or stops charging, which can end a running charge slot early.

Check InOutWRte_RvrtTms (40358) before you go live. The scripts below assume 0. Smart Battery Pilot runs the charge and export scripts at the start of each slot, but the idle and auto scripts only when the mode or the reserve changes. With a timeout of 900 s, a charge in hourly slots therefore stops after 15 minutes, and in 15-minute slots the timeout races the next write. The idle script below is not affected: it holds the battery through MinRsvPct, which has no timeout. A hold built from StorCtl_Mod 2 and OutWRte 0 instead expires after the timeout, and the battery discharges for the rest of the idle block. Either write 0 to 40358, or have the charge and export scripts write a timeout longer than one slot, which keeps a safety net in case Home Assistant stops.

Scripts (scripts.yaml)

The charge and export scripts receive power_w from Smart Battery Pilot and convert it to a rate in hundredths of a percent of WChaMax. Every script also receives reserve_soc — the backup reserve, or the minimum SOC while none is set. The auto script writes it into MinRsvPct (40350) so the Gen24 holds the reserve on its own, even while Home Assistant is down; the idle script raises MinRsvPct to the current SOC so the battery holds what it has. The charge script keeps 99 % there on purpose. max_power is the value of WChaMax (e.g. 12800 from register 40345, the first field of sensor.reading_battery_settings).

sbp_force_charge:
  alias: "SBP: Laden erzwingen"
  fields:
    power_w:
      description: Charge power in W (provided by Smart Battery Pilot)
      default: 6000
  variables:
    max_power: 12800
    rate: "{{ [((power_w | default(6000)) / max_power * 10000) | int, 10000] | min }}"
  sequence:
    # Charge limit (InWRte) at 100 %; not armed by StorCtl_Mod 2 anyway
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40356, value: 10000 }
    # Negative discharge limit (OutWRte) = charge at least at this rate
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40355, value: "{{ 65536 - rate }}" }
    # Keep reserve at 99% so the battery keeps topping up (slowly) even if
    # something resets StorCtl_Mod during the slot
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40350, value: 9900 }
    # Arm the discharge limit (bit 1). 1 would arm only the charge limit and
    # leave the negative OutWRte without effect.
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40348, value: 2 }

sbp_block_discharge:
  alias: "SBP: Entladen sperren (Idle)"
  sequence:
    # No limits armed: PV may still charge, grid-charge from a previous
    # `charge` slot must not continue.
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40348, value: 0 }
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40355, value: 10000 }
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40356, value: 10000 }
    # Hold the battery: MinRsvPct = current SOC (rounded down, so it never
    # sits above the SOC and triggers a grid top-up), at least the backup
    # reserve, at most 98 %. Always rewritten, so a preceding 99 % reserve
    # cannot leak into idle hours.
    # The SOC is the inverter's own ChaState (40351, seventh field of
    # `sensor.reading_battery_settings`), with the battery's SOC sensor as
    # fallback: see "Which SOC the idle script reads" below.
    - service: modbus.write_register
      data:
        hub: gen24
        slave: 1
        address: 40350
        value: >-
          {%- set raw = states('sensor.reading_battery_settings').split(',') -%}
          {%- set inv = (raw[6] | float(0)) / 100 if raw | length > 6 else 0 -%}
          {%- set soc = (inv | int) if 0 < inv <= 100
                else (states('sensor.byd_battery_box_premium_hv_ladezustand') | int(5)) -%}
          {{ [[soc, reserve_soc | default(5) | int] | max, 98] | min * 100 }}

sbp_auto_mode:
  alias: "SBP: Auto-Modus"
  sequence:
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40348, value: 0 }
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40355, value: 10000 }
    # Backup reserve from Smart Battery Pilot (minimum SOC while none is set);
    # the inverter keeps it even while Home Assistant is down.
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40350, value: "{{ ((reserve_soc | default(5)) * 100) | int }}" }
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40356, value: 10000 }

sbp_force_discharge:
  alias: "SBP: Entladen ins Netz erzwingen (Export-Modus)"
  fields:
    power_w:
      description: Discharge power in W (provided by Smart Battery Pilot)
      default: 6000
  variables:
    max_power: 12800
    rate: "{{ [((power_w | default(6000)) / max_power * 10000) | int, 10000] | min }}"
  sequence:
    # Discharge limit (OutWRte) at 100 %; not armed by StorCtl_Mod 1 anyway
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40355, value: 10000 }
    # Negative charge limit (InWRte) = discharge at least at this rate
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40356, value: "{{ 65536 - rate }}" }
    # Arm the charge limit (bit 0)
    - service: modbus.write_register
      data: { hub: gen24, slave: 1, address: 40348, value: 1 }

Which SOC the idle script reads

The hold is only as good as the SOC it is built from. A battery integration that polls once a minute still reports the old value when an idle slot follows a charge slot: the floor then lands a percent or more below the real SOC, and the battery discharges down to it during the first idle minutes — energy that was bought a moment ago. The inverter's own ChaState register updates every few seconds and is the value MinRsvPct is compared against anyway, so the script reads that one and only falls back to the battery's sensor when the register sensor has no usable value.

The pilot's battery discharges in idle slots check reports this kind of leak once it has seen it on several days.

EVCC next to the pilot

sbp_block_discharge holds the battery through MinRsvPct, which EVCC never touches. The alternative, StorCtl_Mod 2 with OutWRte 0 (EVCC's hold), blocks discharging just as well but is undone when EVCC rewrites StorCtl_Mod.

The reverse happens too: while EVCC holds the battery for a car (StorCtl_Mod 2, OutWRte 0), a pilot that keeps writing would fight it. With EVCC on the same inverter, set the EV section to policy External with sensor.evcc_battery_mode (the "[CODE]" sensor of the evcc integration, disabled by default). The pilot then pauses during EVCC's hold and re-applies its own mode afterwards (EV charging). Set Planned EV sessions to evcc as well: the plan then shows EVCC's coming holds ahead of time and plans no grid charge into them, since the pilot would not be allowed to run it there anyway.

sbp_force_discharge follows from the register semantics above (negative InWRte, the mirror image of the verified charge script) but has not been tested on the reference installation. Try it in a short manual run before you let the pilot export.

Integration configuration

Config flow field Entity / value
Price forecast entity sensor.nordpool_kwh_ger_eur_3_10_019 (Nordpool HACS)
Price offset 0.187 EUR/kWh (German grid fees + taxes)
SOC entity sensor.byd_battery_box_premium_hv_ladezustand
Capacity 12.8 kWh
Max charge / discharge power 6000 / 6000 W
Min / Max SOC 10 / 95 %
Efficiency 90 %
Script: force charge script.sbp_force_charge
Script: idle script.sbp_block_discharge
Script: auto script.sbp_auto_mode
Script: export (optional) script.sbp_force_discharge
Consumption sensor sensor.solarnet_leistung_verbrauch (W, Fronius SolarNet)
Temperature sensor sensor.aussen_temperatur
PV forecast today / tomorrow sensor.vorhersage_solarproduktion_gesamt_heute / …_morgen (Open-Meteo Solar Forecast)
Current PV power (optional) e.g. sensor.solarnet_leistung_produktion — shown live on the card
Battery charge / discharge energy (optional) cumulative kWh or Wh meters, both needed for the battery-benefit and pilot-savings sensors and for learning the cold-weather charge limit. Prefer the core Fronius DC counters Battery charging/discharging energy total (HA 2026.9+) over a Riemann sum

Optional features in the options menu:

Option Entity / value
Cold-weather charging on, with the BYD module/cell temperature sensor of your byd_hvs installation as battery temperature; defaults 10/20/50/80/100 % suit the LFP cells — check the BYD datasheet
Backup reserve e.g. 20 %, optionally an input_number your storm-warning automation raises; block discharging is not needed, the Gen24 holds MinRsvPct itself

Verification sensors

Watch these while testing (dry-run first!):

Entity Forced charge Idle
sensor.byd_storctl_mod 2 0
sensor.byd_… OutWRte (40355) 65536 − rate, shown as a negative % 10000
sensor.byd_… MinRsvPct (40350) 9900 (99 %) current SOC × 100, at least reserve_soc × 100
sensor.solarnet_ladeleistung ≈ planned power_w 0 from grid
sensor.byd_battery_box_premium_hv_stromstarke_dc negative (charging) ~0 discharge

Notes

  • The Gen24 occasionally ignores a single Modbus write. If you see this, wrap the writes in a retry (repeat with a stop on success).
  • Negative price handling (stopping PV production below −0.10 EUR/kWh via registers 40232/40236) is independent of this integration and can coexist. From HA 2026.9 the same registers are also number.*_ac_power_limit + switch.*_ac_power_limiting; do not bind both. Core's AC power limit is inverter output, not a grid export cap, and a value below 10 % may put the Gen24 into standby.