Zendure SolarFlow 2400 AC+ (AC-coupled) + separate PV inverter

A plug-in AC battery with no hybrid inverter: the Zendure SolarFlow 2400 AC+ sits on a wall socket and is controlled through Home Assistant via a SolarFlow integration (select/number entities). Rooftop PV runs on a separate Hoymiles micro-inverter (OpenDTU), and the grid meter is a Dutch P1 smart meter read by DSMR Reader → MQTT. Prices come from a Nordpool template sensor.

This setup differs from most others in one important way: nothing in the hardware captures PV surplus by itself. A hybrid inverter in auto mode charges its battery from its own PV; the SolarFlow AC+ in output mode never pulls AC power to charge. The pilot plans auto slots assuming exactly that capture happens, so this example adds a small assist automation that provides bidirectional self-consumption inside auto slots: discharge to cover the house load, charge from surplus otherwise. In the what an auto slot assumes table, this is the row where nobody follows the meter unless an automation does.

Architecture

                    ┌─ charge slot ──▶ sbp_force_charge ──▶ AC mode input,  input_limit = power_w
pilot ──▶ scripts ──┼─ idle slot ───▶ sbp_block_discharge ▶ AC mode output, output_limit = 0
                    └─ auto slot ───▶ sbp_auto_mode ──────▶ AC mode output + assist automation ON
 assist automation (runs only in auto slots):
   house load > 150 W ──────────▶ output mode, output_limit = min(load, max_w)
   PV surplus > 250 W (stable) ▶ input mode,  input_limit  = min(surplus, max_w)
   otherwise ──────────────────▶ output mode, output_limit = 0

The assist is the pilot's "hands" in auto mode only: the charge and idle scripts switch it off before they command the device, so there is exactly one writer to the power limits at any moment. The pilot stays the single brain.

What about the device's own smart-meter mode? With a compatible meter paired in the vendor app, the 2400 AC+ can follow the grid meter on its own — the one case in what an auto slot assumes where the loop closes without an automation. It is still the wrong tool here: the mode lives in the vendor app, is not exposed to Home Assistant by the integration, and it follows the meter in every state — it would keep discharging through charge and idle slots where the plan wants the battery held or charging, trading the plan's price optimization and evening protection for plain load-following. So the battery stays in command mode, and the assist closes the loop instead — only inside auto slots, and only while the pilot has it enabled.

Prerequisites

  • A SolarFlow integration exposing at least:
  • select.…_ac_mode (input / output)
  • number.…_input_limit, number.…_output_limit (W)
  • sensor.…_electric_level (SOC %), sensor.…_output_home_power (W), sensor.…_grid_input_power (W, AC charge draw)
  • Grid power at the meter: sensor.dsmr_reading_electricity_currently_delivered / …_currently_returned (kW) — any whole-house power sensor works
  • The pilot's pv_power_entity set to the inverter's live AC power (OpenDTU)

Entity IDs below use the author's names; yours may differ slightly.

Scripts

sbp_force_charge:
  alias: "SBP: Force charge"
  fields:
    power_w:
      description: Charge power in W
  sequence:
    - action: automation.turn_off
      target:
        entity_id: automation.assist_discharge_on_import
    - action: select.select_option
      target:
        entity_id: select.solarflow_2400_ac_plus_ac_mode
      data:
        option: input
    - action: number.set_value
      target:
        entity_id: number.solarflow_2400_ac_plus_input_limit
      data:
        value: "{{ [power_w | float(0), 800] | min | round(0) }}"
    - action: number.set_value
      target:
        entity_id: number.solarflow_2400_ac_plus_output_limit
      data:
        value: 0

sbp_block_discharge:
  alias: "SBP: Block discharge (idle)"
  sequence:
    - action: automation.turn_off
      target:
        entity_id: automation.assist_discharge_on_import
    - action: select.select_option
      target:
        entity_id: select.solarflow_2400_ac_plus_ac_mode
      data:
        option: output
    - action: number.set_value
      target:
        entity_id: number.solarflow_2400_ac_plus_output_limit
      data:
        value: 0

sbp_auto_mode:
  alias: "SBP: Auto mode"
  sequence:
    - action: select.select_option
      target:
        entity_id: select.solarflow_2400_ac_plus_ac_mode
      data:
        option: output
    - action: automation.turn_on
      target:
        entity_id: automation.assist_discharge_on_import

# optional, only needed for export mode:
sbp_force_discharge:
  alias: "SBP: Force discharge to grid"
  fields:
    power_w:
      description: Discharge power in W
  sequence:
    - action: automation.turn_off
      target:
        entity_id: automation.assist_discharge_on_import
    - action: select.select_option
      target:
        entity_id: select.solarflow_2400_ac_plus_ac_mode
      data:
        option: output
    - action: number.set_value
      target:
        entity_id: number.solarflow_2400_ac_plus_output_limit
      data:
        value: "{{ [power_w | float(0), 800] | min | round(0) }}"

The 2400 AC+ is capped at 800 W per phase on a domestic socket; raise the cap together with the pilot's Battery power limits once your installation allows more.

The assist automation

This is the piece that makes an AC-coupled battery behave like a hybrid in auto slots. It is edge-triggered per grid-meter telegram, with a time-pattern backstop, and it re-derives everything from raw sensor states on every run, so there is no state to get stale.

Two definitions do all the work:

  • gap = delivered − returned + battery output = house load − PV, independent of what the battery is currently doing (while discharging).
  • surplus = PV − house, computed mode-aware: in output mode it is simply −gap; in input mode it is charge draw − gap. This matters — see pitfalls.

The triggers are split per regime — see pitfall 2 for why one combined trigger will go deaf. All four share the same prelude:

{% set del = states('sensor.dsmr_reading_electricity_currently_delivered') | float(0) * 1000 %}
{% set ret = states('sensor.dsmr_reading_electricity_currently_returned') | float(0) * 1000 %}
{% set bout = states('sensor.solarflow_2400_ac_plus_output_home_power') | float(0) %}
{% set bch = states('sensor.solarflow_2400_ac_plus_grid_input_power') | float(0) %}
{% set soc = states('sensor.solarflow_2400_ac_plus_electric_level') | float(0) %}
{% set mode = states('select.solarflow_2400_ac_plus_ac_mode') %}
{% set gap = del - ret + bout %}
{% set surplus = (bch - gap) if mode == 'input' else (-gap) %}
{% set out = states('number.solarflow_2400_ac_plus_output_limit') | float(0) %}
{% set inl = states('number.solarflow_2400_ac_plus_input_limit') | float(0) %}
alias: "Assist: discharge on import, charge on surplus"
mode: restart
triggers:
  # 1. discharge desired (house load > 150 W) and diverges from actual
  - trigger: template
    value_template: >
      {% set del = ... %} {% set ret = ... %} {% set bout = ... %}
      {% set soc = ... %} {% set mode = ... %} {% set gap = del - ret + bout %}
      {% set out = states('number.solarflow_2400_ac_plus_output_limit') | float(0) %}
      {{ gap > 150 and (mode != 'output' or (([gap, 800] | min | round(0)) - out) | abs > 50) }}
  # 2. charge entry: surplus first exceeds 250 W while in output mode
  - trigger: template
    value_template: >
      {% set del = ... %} {% set ret = ... %} {% set bout = ... %}
      {% set soc = ... %} {% set mode = ... %} {% set gap = del - ret + bout %}
      {{ mode != 'input' and soc < 100 and (-gap) > 250 }}
  # 3. charge adjust: while charging, true surplus drifted >50 W from the limit
  - trigger: template
    value_template: >
      {% set del = ... %} {% set ret = ... %} {% set bout = ... %} {% set bch = ... %}
      {% set soc = ... %} {% set mode = ... %} {% set gap = del - ret + bout %}
      {% set surplus = (bch - gap) if mode == 'input' else (-gap) %}
      {% set inl = states('number.solarflow_2400_ac_plus_input_limit') | float(0) %}
      {{ mode == 'input' and soc < 100 and surplus > 100
         and (([surplus, 800] | min | round(0)) - inl) | abs > 50 }}
  # 4. neutral: neither direction warranted but device is not at rest
  - trigger: template
    value_template: >
      {% set del = ... %} {% set ret = ... %} {% set bout = ... %} {% set bch = ... %}
      {% set soc = ... %} {% set mode = ... %} {% set gap = del - ret + bout %}
      {% set surplus = (bch - gap) if mode == 'input' else (-gap) %}
      {% set out = states('number.solarflow_2400_ac_plus_output_limit') | float(0) %}
      {{ (mode != 'output' or out != 0)
         and gap <= 150
         and surplus <= (100 if mode == 'input' else 250) }}
  # backstop after restarts or missed telegrams
  - trigger: time_pattern
    minutes: "/5"
conditions: []
actions:
  - choose:
      # discharge branch - condition re-evaluated at run time, gap > 150
      - conditions:
          - >
            {% set del = ... %} {% set ret = ... %} {% set bout = ... %}
            {{ (del - ret + bout) > 150 }}
        sequence:
          - action: number.set_value
            target:
              entity_id: number.solarflow_2400_ac_plus_output_limit
            data:
              value: >
                {% set gap = states('sensor.dsmr_reading_electricity_currently_delivered') | float(0) * 1000 - states('sensor.dsmr_reading_electricity_currently_returned') | float(0) * 1000 + states('sensor.solarflow_2400_ac_plus_output_home_power') | float(0) %}
                {% set soc = states('sensor.solarflow_2400_ac_plus_electric_level') | float(0) %}
                {{ [gap, 800] | min | round(0) if soc > 5 and gap > 150 else 0 }}
          - action: select.select_option
            target:
              entity_id: select.solarflow_2400_ac_plus_ac_mode
            data:
              option: output
      # charge branch - true surplus (mode-aware) above the hold threshold
      - conditions:
          - >
            {% set del = ... %} {% set ret = ... %} {% set bout = ... %} {% set bch = ... %}
            {% set gap = del - ret + bout %}
            {% set surplus = (bch - gap) if is_state('select.solarflow_2400_ac_plus_ac_mode', 'input') else (-gap) %}
            {{ states('sensor.solarflow_2400_ac_plus_electric_level') | float(0) < 100
               and surplus > (100 if is_state('select.solarflow_2400_ac_plus_ac_mode', 'input') else 250) }}
        sequence:
          - action: number.set_value
            target:
              entity_id: number.solarflow_2400_ac_plus_input_limit
            data:
              value: >
                {% set del = ... %} {% set ret = ... %} {% set bout = ... %} {% set bch = ... %}
                {% set gap = del - ret + bout %}
                {% set surplus = (bch - gap) if is_state('select.solarflow_2400_ac_plus_ac_mode', 'input') else (-gap) %}
                {{ [surplus, 800] | min | round(0) }}
          - action: select.select_option
            target:
              entity_id: select.solarflow_2400_ac_plus_ac_mode
            data:
              option: input
          - action: number.set_value
            target:
              entity_id: number.solarflow_2400_ac_plus_output_limit
            data:
              value: 0
    default:
      # neutral: output mode, 0 W
      - action: number.set_value
        target:
          entity_id: number.solarflow_2400_ac_plus_output_limit
        data:
          value: 0
      - action: select.select_option
        target:
          entity_id: select.solarflow_2400_ac_plus_ac_mode
        data:
          option: output

(The ... marks stand for the full states(...) | float(0) expressions shown in the prelude above — write them out in your actual YAML.)

Tuning: the 150 W discharge floor ignores noise and tiny loads; the 250 W charge entry / 100 W charge hold pair is the hysteresis that keeps the AC relay from chattering when surplus hovers near the threshold. The 5% SOC floor matches a pilot Min SOC of 5 % (its default is 10 %); the device's own minimum-SOC setting stays in place as the hardware backstop. The choose conditions re-evaluate the regime at run time, so when two triggers fire around the same moment the newest run always acts on the freshest regime.

Two pilot limits need one line each. Max SOC — the assist charges while soc < 100, so set the pilot's Max SOC to 100 % (its default is 95 %) or change the checks to match; otherwise the plan stops at Max SOC while the assist charges on toward 100 %. Backup reserve — the fixed 5 % floor ignores reserve_soc; switch on block discharging at the reserve and the pilot runs the block-discharge script at the reserve, which turns the assist off, so the assist can never drain a configured reserve.

Integration configuration

Config flow field Entity / value
Price forecast entity Nordpool-based template sensor (market + markup, incl. VAT)
SOC entity sensor.solarflow_2400_ac_plus_electric_level
Capacity 5.28 kWh
Max charge / discharge power 800 / 800 W (socket-limited)
Min / Max SOC 5 / 100 % (the assist's floor and ceiling)
Scripts the four sbp_* scripts above
Consumption sensor DSMR-based whole-house load template sensor
PV power entity OpenDTU inverter AC power

Verification

  • Charge slot: grid_input_power tracks power_w; the meter's delivered power rises by the same amount.
  • Auto + surplus: AC mode flips to input, grid_input_power ≈ surplus, and the meter's returned power drops to ≈ 0.
  • Auto + load: output_home_power ≈ house load (up to the cap), returned power ≈ 0, delivered ≈ 0.
  • Regime flips: a cloud edge or a big load stepping on must switch the device within one or two meter telegrams. If a wrong state persists for minutes, your triggers have latched — see pitfall 2.
  • Sunny-day check: the plan's SOC forecast should now track reality. If the forecast rises but the battery does not charge, your capture piece is not working — that is exactly the failure mode this example fixes.
  • Per-phase meter data (DSMR v5 meters publish phase_currently_delivered_l*) tells you which phase a single-phase battery actually lands on.

Notes / pitfalls

  1. Compute surplus mode-aware — never reuse the gap. A natural first draft adds the charge draw into the gap (gap = delivered − returned + output + charge). But delivered − returned already contains the charge draw, so the gap inflates by 2× the charge power: charging starts, the gap jumps over the exit threshold, the automation drops out of charge, the draw decays, the gap falls back under the entry threshold, charging restarts — a self-sustaining oscillation. Measured on a real installation: 14 AC-mode flips in 6 minutes with charge never holding, versus 0 flips and steady full-power charging with the mode-aware formula.
  2. Split the triggers per regime — one combined trigger goes deaf. A template trigger only fires on a false→true edge. A combined trigger that renders true for "charge adjust wanted" and stays true when the regime flips to "discharge wanted" never fires again: no false→true edge happens, because it was already true. Measured on a real installation: a cloud edge plus a washing machine pushed the house from exporting to importing 2.3 kW while the battery kept charging — for 4 minutes, until the 5-minute backstop finally rescued it. Four per-regime triggers (discharge divergence, charge entry, charge adjust, neutral) guarantee every regime change produces a fresh false→true edge, and the backstop stays as a last resort.
  3. Order actions so a cancelled run is harmless. With mode: restart a new trigger cancels a running sequence mid-flight on a fast-swinging load. Write the power limit before the mode switch: the worst case then leaves a fresh limit sitting in the mode where the device ignores it — never a blind mode switch with a stale limit.
  4. The AC relay will click on swingy loads. A washing machine's element cycling under broken clouds swings the house balance by kilowatts in seconds, and the assist follows it. That is the intended bidirectional behavior; energy loss per flip is seconds of dead time, and the vendor firmware tolerates the switching rate. Widen the hysteresis if it bothers you.
  5. Keep the device's minimum SOC as the backstop. The assist floor (5%) mirrors the pilot's planning floor; the Zendure's own setting still stops the hardware even if every automation is wrong.
  6. Export stays off on a socket install (grid_reverse forbidden); the example assumes discharge mode self_consumption.
  7. SOC reports integer percent (1% ≈ 53 Wh on 5.28 kWh) — small charge movements are invisible in SOC; verify via power sensors instead.