How the optimizer works

The planner is deliberately deterministic — no neural network, no solver dependency. Every decision can be explained from the price curve, and the same inputs always produce the same plan.

Inputs

  • Price slots for the next 24–36 h (native resolution of your tariff source, usually 15 min or 1 h), including your configured price offset.
  • Net demand forecast per slot: learned consumption minus expected PV.
  • Battery state: SOC, capacity, min/max SOC, charge/discharge power limits, roundtrip efficiency.
  • Options: minimum price spread, discharge mode, feed-in tariff.
  • Charge factor (cold-weather charging, off by default): the share of the max charge power the battery is expected to accept at its current temperature. It scales the per-slot charge cap, so a cold battery is charged over more slots. A slot planned up to its cold limit asks the charge script for the maximum power, so the pilot never throttles the battery itself — the BMS caps it. A slot that needs less asks for its planned power: a cold BMS caps the current rather than taking a share of the request, so asking for more would overshoot the plan and max SOC.
  • Backup reserve (off by default): the planner counts stored energy above the reserve instead of above the minimum SOC, so no discharge or export slot ever takes the SOC below it. A SOC under the reserve starts as a deficit. Before any arbitrage, a refill pass covers it by the deadline: forecast PV surplus first, the rest in the cheapest grid slots up to the deadline, regardless of the spread. The refill is mandatory, so its cost is excluded from the savings estimate, and the do-nothing baseline gets the same refill — both sides compare arbitrage against arbitrage. Finishing the refill earlier, at a higher price, is weighed against the arbitrage it opens up (see step 0); what it costs on top of the cheapest refill counts against the savings.
  • Planned EV sessions (off by default, evcc only): the energy the car is expected to draw per slot, and whether the EV policy holds the battery in that slot. See EV sessions in the plan.

Algorithm

Greedy pairing with a stored-energy timeline simulation. Stored energy is counted above a floor — the minimum SOC, or the backup reserve when one is set — and each slot's charge capacity is the max charge power scaled by the cold-weather charge factor.

  1. Refill the backup reserve (only if the SOC is below it): forecast PV first, then the cheapest grid slots up to the refill deadline, regardless of the spread. These become ordinary charge slots. Until the refill the battery may spend nothing, so a cheap slot behind a price peak gives that peak away. The planner therefore also tries finishing the refill earlier — in front of each slot worth more, after losses, than the cheapest slot before it — runs steps 1–3 for each of these refills, and keeps the cheapest whole plan. On a tie it keeps the latest deadline.
  2. Sort the uses of battery energy by value, most valuable first. These are the discharge candidates. Covering a slot's net demand is worth its import price. In export mode, selling into the grid in a slot is a second candidate, worth the sell price minus the spread. Both kinds compete for the same stored energy in this one list, so a cheap night cannot drain the battery before a much pricier export peak is considered. The spread discount keeps a slot's demand covered unless exporting the energy elsewhere clearly pays more.
  3. For each candidate, the energy it needs is sourced:
    1. from energy already in the battery (PV surplus, initial SOC) — free energy always goes to the most valuable use first;
    2. from grid charging in cheaper, earlier slots — only if charge price / efficiency + spread < discharge price (the sell price for an export), and never while the battery would still be below an unfilled reserve at that slot.
  4. Every assignment is validated against the battery timeline: SOC never leaves the window between the floor and max SOC at any point, and per-slot charge/discharge power limits are respected. Forecasted PV surplus charges the battery in this timeline (clamped at max SOC, limited by charge power) — so on sunny days the planner knows the battery refills by evening, doesn't lock it during the day and doesn't grid-charge needlessly. PV occupies the slot's charge-power headroom first; grid charging in the same slot only uses what is left. The SOC projection rises with the sun accordingly. See what an auto slot assumes.
  5. Curtailed PV makes earlier energy free to spend. Where the timeline pins the battery at max SOC, the surplus that no longer fits is thrown away. A kWh discharged before such a slot is refilled by that surplus at no cost, so it leaves every later SOC level untouched — the timeline check in step 3 credits each candidate with the curtailed energy between it and the slots it would otherwise starve. Without this, holding energy back for a morning peak on a sunny day displaces free midday PV with energy bought from the grid, and the plan ends the day having delivered less to the house than an untouched inverter.
  6. Held energy is rerouted when a later charge can replace it. Free energy went to the most valuable slots first, wherever they lie. An earlier slot then only finds charge slots before itself, and stays on the grid when those are expensive — while the battery carries energy straight through it. Typical case: an evening at a middling price, a cheap night, an expensive morning. If a charge slot in between satisfies the same spread rule against the earlier slot, that slot is covered from the held energy and the charge slot buys the same amount back. Every SOC level from the charge slot on stays as it was, so nothing planned later changes.
  7. Slots that have real demand but whose stored energy the assignment did not spend are marked idle (discharge blocked): the energy is reserved for a later, more expensive slot, so the battery must not be drained early. The label follows from the assignment rather than being re-derived beside it, which is what keeps the inverter's behaviour and the cost model in agreement. Slots with PV surplus stay in auto — the inverter charges from PV and won't discharge anyway.
  8. In export mode, the export candidates from step 1 turn peak slots into export slots. Export is valued at the feed-in tariff (or the raw market price if 0 — the configured import offset is not counted as export revenue). An export script is required for this mode; the options flow refuses to select it without one. What the cost model assumes of that script is spelled out under Export slots below.
  9. Never worse than doing nothing. If the finished plan's estimated savings still come out negative, it is discarded and the all-auto plan is returned instead, carrying a plan_worse_than_baseline warning in the plan sensor's attributes. Leaving the inverter alone is always available and is the very baseline the figure is measured against.

The plan is recomputed every 30 minutes, whenever the price entity or the backup-reserve entity updates (e.g. tomorrow's prices arriving around 14:00), on option changes, and via the smart_battery_pilot.replan service. Only the current slot's action is ever executed, so plan revisions take effect immediately.

EV sessions in the plan

With planned EV sessions (see EV charging) each slot carries the energy the car is expected to draw. The car sits on the same AC bus as the house:

  • It takes PV surplus first. That share no longer reaches the battery, so the SOC forecast does not rise on PV the car eats.
  • Whatever it draws beyond that comes from the grid, or from the battery when the EV policy is Allow: then it is ordinary demand, and the planner decides whether the battery serves it or saves its energy for a pricier slot.
  • With Block (above the threshold) or External (evcc may hold the battery), the slot is held: no discharge there, and the car's grid energy is not demand the battery could cover. It costs the same with or without the plan, so it is left out of both sides of the savings estimate.
  • With External the pilot cannot grid charge in a held slot either: it calls no script while evcc holds the battery. PV still charges it, since a hold only stops discharging.
  • With a grid import limit, a slot's grid charge is capped at the limit minus the forecast house demand and the car's grid energy. PV surplus is not grid import and is not capped.

A held slot stays auto in the plan rather than turning idle. The wallbox block or evcc holds the battery exactly while the car really draws; an idle would keep it blocked for a session that ends early or never starts.

What an auto slot assumes

The pilot only plans an auto slot; it does not regulate anything inside it. The plan assumes that something else keeps the grid meter near zero during the slot: the battery covers the house load, and PV surplus charges the battery.

What matters is who closes that loop, not whether the PV is DC- or AC-coupled:

Installation Who follows the grid meter in auto
Hybrid inverter, PV on its DC input The inverter
Hybrid inverter, more PV on the AC side The inverter, if it has a grid meter and is allowed to charge from other generators (often a setting)
AC battery in its smart-meter mode The battery
AC battery that only follows charge and discharge commands Nobody, unless an automation does it

If nothing closes the loop, the plan and the battery drift apart without any error:

  • The SOC forecast rises with the sun, but the battery does not. Every re-plan starts again from the real SOC and quietly shrinks what is left for the evening.
  • Grid charging is skipped. The evening demand counts as covered by PV energy that never arrives.
  • Surplus goes to the grid while the battery is far from full.

The pilot reports this once it has seen it on several days, if it has a live PV sensor (consistency checks). To check an installation yourself, watch one sunny auto slot with the battery well below max SOC: the grid meter should show next to no export, and the SOC should rise. If you close the loop with an automation, have the auto script enable it and the other scripts disable it before they command the battery, so that only one writer is active at a time. It also has to respect the pilot's limits: stop charging at max SOC, and stop discharging at reserve_soc, or switch on block discharging at the reserve.

What an export slot assumes

An export slot is the one action where the plan asks the inverter to do two things at once. The cost model still credits the household load as covered from the battery and charges only the remainder to the grid at the feed-in price — and the power_w handed to the export script is the sum of both, the load share plus the exported share.

Your export script must therefore keep serving the house from the battery while it discharges into the grid. A script that switches the inverter to a pure "sell at power_w" mode and leaves the house on the grid meter still runs safely, but the household demand of those slots is then bought at the import price without the model knowing, and the realised saving comes out below estimated_savings by that demand times the import price. A peak can span several consecutive export slots, so if your inverter cannot do both, prefer self-consumption mode.

What curtailed PV is worth

Where the timeline pins the battery at max SOC, the surplus that no longer fits is treated as worth nothing — step 4 above spends energy freely ahead of such a slot because the PV refills it at no cost. In reality that surplus is exported and earns the feed-in tariff, so those withdrawals do have a price.

It does not change any decision. The withdrawal happens to avoid an import, and as long as the import price exceeds the feed-in tariff — which it does in every residential tariff this integration targets — spending stored energy before a curtailment window is the better trade regardless. It makes estimated_savings a touch optimistic on sunny days with a fixed feed-in tariff, by at most the feed-in value of the energy moved.

Why a spread threshold?

Every grid-charged kWh loses ~10 % to conversion and costs battery cycle life. With spread s and efficiency η, charging at price p_c for a discharge at p_d only happens if

p_c / η + s  <  p_d

The default s = 0.20 EUR/kWh means: a night price of 0.10 with 90 % efficiency requires an evening price above ~0.31 before the battery is charged from the grid.

Savings estimate

sensor.…_estimated_savings compares the plan's grid bill against the bill you would get from doing nothing — plain self-consumption, the inverter's own behaviour:

grid cost = Σ (demand − battery kWh delivered) × slot price
          + Σ grid-charged kWh × slot price
          − Σ exported kWh × sell price

savings   = grid cost (do nothing) − grid cost (plan)

The baseline matters. Valuing every discharged kWh against "buy everything from the grid" would report a fat saving even for an all-auto plan that changes nothing, because a battery covering the house is what the inverter does anyway. With the do-nothing baseline, a plan that changes nothing reports 0.00, and what is left is the part the planner actually earned: charging cheap, and holding energy back for a pricier hour.

It is an estimate over the current plan horizon, not a billing-grade number. The sensor is a point-in-time MEASUREMENT (it jumps at every replan), not an accumulating meter — and deliberately carries no monetary device class, which Home Assistant only accepts together with TOTAL. Three running totals come from the battery's energy meters. They answer three different questions:

Sensor Question How it counts
Battery benefit (net) (sensor.…_actual_savings_eur, id kept from before the rename) What is the battery worth? Discharge credited at what it displaced (the import price; in an export slot the feed-in tariff, or the raw market price when that is 0), minus what the charge cost: grid charge at the import price, PV charge in auto/idle at the feed-in tariff it displaced. A charge in a pilot mode not yet on record is priced at the import price.
Battery benefit (gross) (sensor.…_battery_gross_eur) What did the battery displace? Discharge only, valued the same way. Charge costs, including the PV opportunity cost, are not deducted.
Pilot savings (sensor.…_pilot_savings_eur) What did the pilot add? Only energy the pilot moved differently from the inverter: grid charge in a charge slot, and demand an idle slot kept the battery from covering (estimated from the plan's demand forecast). Each goes into a lot with its price. Later discharge uses the lots oldest first and is credited with the value then, minus that price, after losses. Discharge beyond the lots is plain self-consumption and earns the pilot nothing. A pilot that only ever sends auto therefore shows 0.00. A trade that did not pay off lowers the figure.

Net and gross count whether or not the pilot steers. With the pilot off or in dry-run, the inverter runs in its own (auto) mode, and the energy is priced that way. The pilot savings are booked segment by segment, at every slot boundary and mode change. The lots never exceed the energy the battery actually holds above the minimum SOC, and they appear in the diagnostics dump. Wh meters are converted to kWh. All totals keep their last value when an update fails, so a blinking price entity does not tear a hole in their long-term statistics.

None of these is a counterfactual against the inverter's own behaviour. That cannot be measured. estimated_savings is the one with a simulated do-nothing baseline, over the plan horizon.

Worked example (Dunkelflaute)

Prices: night 0.10, morning peak 0.45, day 0.20, evening peak 0.50 EUR/kWh. Demand 1.5 kWh/h, battery 12.8 kWh / 6 kW, SOC 10 %, spread 0.10:

  • The evening peak (0.50) is paired first → charged in the cheapest night slots (0.10 / 0.9 + 0.10 = 0.21 < 0.50 ✓).
  • The morning peak (0.45) is paired next, also from night slots.
  • Day slots at 0.20 stay idle — discharging there would waste energy worth 0.50 in the evening.
  • Result: charge at night, auto during both peaks, idle in between.